Amps to kVA Calculator

Turn a current in amps into kVA for a single phase or 3 phase supply. It's ideal for sizing a generator from your incoming supply or measured load. Results update as you type.

Single phase: kVA = (I × V) ÷ 1000

3 phase: kVA = (√3 × I × V) ÷ 1000

Where: kVA = apparent power · I = current in amps (per phase for 3 phase) · V = voltage (line-to-line for 3 phase) · √3 ≈ 1.732

Example: 100A per phase, 3 phase 400V: 1.732 × 100 × 400 ÷ 1000 = 69.3 kVA

Convert Amps to kVA

⇄ Switch to kVA to Amps
Phase

UK mains: 230V single phase, 400V 3 phase (line-to-line). 110V is used for site tools.

No power factor needed: kVA already includes it.

Apparent power

69.28 kVA

1.732 × 100A × 400V ÷ 1000 = 69.28 kVA

Nearest generator size: 80 kVA Generators

Recommended withheadroom (86.6 kVA): 90 kVA Generators

Headroom covers motor start-up surges and future load growth. 20-25% is typical.

Amps to kVA conversion table: single phase

Amps to kVA, single phase 230V
AmpskVA
5A1.15
10A2.3
13A2.99
16A3.68
20A4.6
25A5.75
32A7.36
40A9.2
50A11.5
63A14.49
80A18.4
100A23

Amps to kVA conversion table: 3 phase

Amps per phase to kVA, 3 phase 400V
Amps per phasekVA
16A11.09
32A22.17
63A43.65
100A69.28
125A86.6
160A110.85
200A138.56
250A173.21
315A218.24
400A277.13
500A346.41
630A436.48
800A554.26
1000A692.82
1250A866.03
1600A1108.51
2000A1385.64
2500A1732.05
3200A2217.03
4000A2771.28

How to convert amps to kVA

To convert amps to kVA you need the current, the voltage and whether the supply is single phase or 3 phase. No power factor is needed.

  1. Find the current. Use the rating of your supply or main breaker, a clamp-meter reading, or the equipment's data plate.
  2. Pick the formula. Single phase: kVA = amps × volts ÷ 1000. 3 phase: kVA = 1.732 × amps × volts ÷ 1000.
  3. Use the per-phase current for 3 phase. Don't add the three phases together.
CurrentSupplyCalculationkVA
63ASingle phase 230V63 × 230 ÷ 100014.5 kVA
100ASingle phase 230V100 × 230 ÷ 100023 kVA
100A per phase3 phase 400V1.732 × 100 × 400 ÷ 100069.3 kVA
400A per phase3 phase 400V1.732 × 400 × 400 ÷ 1000277.1 kVA
1600A per phase3 phase 400V1.732 × 1600 × 400 ÷ 10001108.5 kVA

Sizing a standby generator from your supply's amp rating

A quick way to estimate the generator size for a building is to convert its incoming supply rating from amps to kVA:

  • A typical UK home has a single phase supply fused at 60-100A. At 230V, 100A is 23 kVA, though most homes use far less than their fuse rating. See our generators for homes.
  • A small commercial unit with a 100A 3 phase supply has a capacity of about 69 kVA, so an 80 kVA generator would cover the full supply.
  • A larger site with a 400A 3 phase supply is around 277 kVA. A 300 kVA generator covers it, with more headroom from a 350 kVA generator.

Sizing to the supply rating is the cautious approach. If you know your actual maximum demand, from half-hourly meter data or clamp-meter readings taken at peak times, convert that figure instead. It often allows a smaller, more economical standby generator.

Matching the generator to your changeover switch

Changeover switches and automatic transfer switch (ATS) panels are rated in amps, not kVA. Converting between amps and kVA lets you check that the generator and the switch suit each other: the switch must be rated for at least the generator's full-load current, and usually for the incoming supply too.

Common mistakes

  • Adding the phases together. A 100A 3 phase supply means 100A on each phase, not 300A in total. The √3 in the formula already accounts for all three phases.
  • Using the wrong voltage. UK 3 phase is 400V line-to-line. Using 230V in the 3 phase formula understates the kVA.
  • Forgetting starting currents. Motors draw a high inrush current at start-up. If your load includes big motors, allow extra headroom or ask us to check.

Amps to kVA FAQs

How many kVA is 100 amps?

On a 3 phase 400V supply, 100A per phase is 69.3 kVA. On a single phase 230V supply, 100A is 23 kVA.

How do I convert amps to kVA in 3 phase?

Multiply the current per phase by the line-to-line voltage and by 1.732 (√3), then divide by 1000. For example, 63A at 400V = 1.732 × 63 × 400 ÷ 1000 = 43.6 kVA.

Can I add the amps on each phase together?

No. Use the current on one phase. If the phases are unbalanced, use the highest reading so the generator can handle the most heavily loaded phase.

What size generator do I need for a 63A 3 phase supply?

63A at 400V is 43.6 kVA. With around 25% headroom that's about 54.5 kVA, so a 60 kVA generator would be a sensible starting point.

Do I need the power factor to convert amps to kVA?

No. You only need the power factor to convert amps to kW. For that, use our Amps to kW calculator.

Need help sizing a generator?

Tell us what you need to power and our team will recommend the right generator, with prices up front.