Turn a current in amps into kVA for a single phase or 3 phase supply. It's ideal for sizing a generator from your incoming supply or measured load. Results update as you type.
Single phase: kVA = (I × V) ÷ 1000
3 phase: kVA = (√3 × I × V) ÷ 1000
Where: kVA = apparent power · I = current in amps (per phase for 3 phase) · V = voltage (line-to-line for 3 phase) · √3 ≈ 1.732
Example: 100A per phase, 3 phase 400V: 1.732 × 100 × 400 ÷ 1000 = 69.3 kVA
UK mains: 230V single phase, 400V 3 phase (line-to-line). 110V is used for site tools.
No power factor needed: kVA already includes it.
Apparent power
69.28 kVA
1.732 × 100A × 400V ÷ 1000 = 69.28 kVA
Nearest generator size: 80 kVA Generators
Recommended withheadroom (86.6 kVA): 90 kVA Generators
Headroom covers motor start-up surges and future load growth. 20-25% is typical.
| Amps | kVA |
|---|---|
| 5A | 1.15 |
| 10A | 2.3 |
| 13A | 2.99 |
| 16A | 3.68 |
| 20A | 4.6 |
| 25A | 5.75 |
| 32A | 7.36 |
| 40A | 9.2 |
| 50A | 11.5 |
| 63A | 14.49 |
| 80A | 18.4 |
| 100A | 23 |
| Amps per phase | kVA |
|---|---|
| 16A | 11.09 |
| 32A | 22.17 |
| 63A | 43.65 |
| 100A | 69.28 |
| 125A | 86.6 |
| 160A | 110.85 |
| 200A | 138.56 |
| 250A | 173.21 |
| 315A | 218.24 |
| 400A | 277.13 |
| 500A | 346.41 |
| 630A | 436.48 |
| 800A | 554.26 |
| 1000A | 692.82 |
| 1250A | 866.03 |
| 1600A | 1108.51 |
| 2000A | 1385.64 |
| 2500A | 1732.05 |
| 3200A | 2217.03 |
| 4000A | 2771.28 |
To convert amps to kVA you need the current, the voltage and whether the supply is single phase or 3 phase. No power factor is needed.
| Current | Supply | Calculation | kVA |
|---|---|---|---|
| 63A | Single phase 230V | 63 × 230 ÷ 1000 | 14.5 kVA |
| 100A | Single phase 230V | 100 × 230 ÷ 1000 | 23 kVA |
| 100A per phase | 3 phase 400V | 1.732 × 100 × 400 ÷ 1000 | 69.3 kVA |
| 400A per phase | 3 phase 400V | 1.732 × 400 × 400 ÷ 1000 | 277.1 kVA |
| 1600A per phase | 3 phase 400V | 1.732 × 1600 × 400 ÷ 1000 | 1108.5 kVA |
A quick way to estimate the generator size for a building is to convert its incoming supply rating from amps to kVA:
Sizing to the supply rating is the cautious approach. If you know your actual maximum demand, from half-hourly meter data or clamp-meter readings taken at peak times, convert that figure instead. It often allows a smaller, more economical standby generator.
Changeover switches and automatic transfer switch (ATS) panels are rated in amps, not kVA. Converting between amps and kVA lets you check that the generator and the switch suit each other: the switch must be rated for at least the generator's full-load current, and usually for the incoming supply too.
On a 3 phase 400V supply, 100A per phase is 69.3 kVA. On a single phase 230V supply, 100A is 23 kVA.
Multiply the current per phase by the line-to-line voltage and by 1.732 (√3), then divide by 1000. For example, 63A at 400V = 1.732 × 63 × 400 ÷ 1000 = 43.6 kVA.
No. Use the current on one phase. If the phases are unbalanced, use the highest reading so the generator can handle the most heavily loaded phase.
63A at 400V is 43.6 kVA. With around 25% headroom that's about 54.5 kVA, so a 60 kVA generator would be a sensible starting point.
No. You only need the power factor to convert amps to kW. For that, use our Amps to kW calculator.
Tell us what you need to power and our team will recommend the right generator, with prices up front.
Cummins C55D5EQ

Cummins C55D5EQ
Cummins C55D5e

Cummins C55D5e
Cummins C66D5EQ

Cummins C66D5EQ
Cummins C66D5e

Cummins C66D5e