Amps to kW Calculator

Convert a current in amps to kilowatts for single phase or 3 phase supplies. It's useful for turning clamp-meter readings or supply ratings into a generator size. Results update as you type.

Single phase: kW = (I × V × PF) ÷ 1000

3 phase: kW = (√3 × I × V × PF) ÷ 1000

Where: kW = real power · I = current in amps (per phase for 3 phase) · V = voltage (line-to-line for 3 phase) · PF = power factor · √3 ≈ 1.732

Example: 100A per phase, 3 phase 400V, PF 0.8: 1.732 × 100 × 400 × 0.8 ÷ 1000 = 55.4 kW

Convert Amps to kW

⇄ Switch to kW to Amps
Phase

UK mains: 230V single phase, 400V 3 phase (line-to-line). 110V is used for site tools.

Diesel generators are rated at 0.8 PF. Use 1.0 for purely resistive loads such as heaters.

Real power

55.43 kW

1.732 × 100A × 400V × 0.8 ÷ 1000 = 55.43 kW

70 kW Generators covers 55.43 kW withheadroom

Headroom covers motor start-up surges and future load growth. 20-25% is typical.

Amps to kW conversion table: single phase

Amps to kW, single phase 230V, PF 0.8
AmpskW
5A0.92
10A1.84
13A2.39
16A2.94
20A3.68
25A4.6
32A5.89
40A7.36
50A9.2
63A11.59
80A14.72
100A18.4

Amps to kW conversion table: 3 phase

Amps per phase to kW, 3 phase 400V, PF 0.8
Amps per phasekW
16A8.87
32A17.74
63A34.92
100A55.43
125A69.28
160A88.68
200A110.85
250A138.56
315A174.59
400A221.7
500A277.13
630A349.18
800A443.41
1000A554.26
1250A692.82
1600A886.81
2000A1108.51
2500A1385.64
3200A1773.62
4000A2217.03

How many kW in an amp?

One amp is worth a different number of kilowatts depending on the voltage, the phase and the power factor:

SupplyPF 1.0 (resistive)PF 0.8 (typical generator load)
Single phase 230V0.23 kW0.184 kW
Single phase 110V (site tools)0.11 kW0.088 kW
3 phase 400V (per phase amp)0.693 kW0.554 kW

Multiply by your current to get a quick estimate. For example, 100A per phase on a 3 phase 400V supply at 0.8 PF is about 55.4 kW.

How to convert amps to kW

  1. Find the current. Use a clamp-meter reading, the supply or breaker rating, or the equipment data plate.
  2. Confirm the voltage and phase. In the UK that's usually 230V single phase or 400V 3 phase.
  3. Choose a power factor. Use 0.8 for mixed loads with motors, or 1.0 for purely resistive loads like heaters.
  4. Calculate. Single phase: kW = amps × volts × PF ÷ 1000. 3 phase: kW = 1.732 × amps × volts × PF ÷ 1000.
CurrentSupplyCalculationkW
13ASingle phase 230V, PF 1.013 × 230 ÷ 10002.99 kW
32ASingle phase 230V, PF 0.832 × 230 × 0.8 ÷ 10005.89 kW
63A per phase3 phase 400V, PF 0.81.732 × 63 × 400 × 0.8 ÷ 100034.9 kW
250A per phase3 phase 400V, PF 0.81.732 × 250 × 400 × 0.8 ÷ 1000138.6 kW

Sizing a generator from measured amps

If you can measure your load, converting amps to kW is one of the most reliable ways to size a generator:

  1. Measure each phase at peak times with a clamp meter, ideally while your largest equipment is running.
  2. Take the highest phase reading. The generator has to carry the most heavily loaded phase.
  3. Convert to kW with the calculator above.
  4. Add headroom. For example, a highest reading of 120A per phase at 400V and 0.8 PF is 66.5 kW. Adding 25% gives 83.1 kW, so a 100 kW generator is the next size up.

To see the result in kVA rather than kW, which is how many generators are rated, use our Amps to kVA calculator.

Amps to kW vs amps to kVA

Converting amps to kVA gives the apparent power and needs no power factor. Converting amps to kW gives the real power, the useful work being done, so it needs the power factor. For generator sizing, check both: the kW against the engine rating and the kVA against the alternator rating. ATS panels and changeover switches are rated in amps, so keep your original amp figure to hand when choosing switchgear.

Amps to kW FAQs

How many kW is 100 amps?

On a 3 phase 400V supply at 0.8 PF, 100A per phase is 55.4 kW. On a single phase 230V supply at 0.8 PF it's 18.4 kW, or 23 kW at unity power factor.

How many kilowatts are in an amp?

At 230V single phase, one amp is 0.23 kW at unity power factor. At 400V 3 phase and 0.8 PF, one amp per phase is about 0.554 kW.

Can I convert amps to kW without the power factor?

Not exactly. Without the power factor you can only calculate kVA. If you don't know it, use 0.8 for typical mixed loads, or 1.0 for heaters and other resistive loads.

Which amp reading should I use for 3 phase?

Use the current on one phase, not the total of all three. If the readings differ, use the highest so the generator can handle the busiest phase.

What generator do I need for 200 amps 3 phase?

200A per phase at 400V and 0.8 PF is 110.9 kW (138.6 kVA). With 25% headroom you'd look at around 139 kW or 173 kVA, such as a 150 kW generator or a 200 kVA generator.