kVA to kWh & kWh to kVA Calculator

kVA measures power and kWh measures energy, so converting between them needs a run time. Enter the generator size, load and hours to find the energy produced. Or switch direction to find the kVA you need for a given amount of energy.

kWh = kVA × PF × load % × hours

kVA = kWh ÷ (hours × PF × load %)

Where: kWh = energy in kilowatt-hours · kVA = generator rating · PF = power factor (0.8 for diesel generators) · load % = average loading of the generator · hours = run time

Examples:

  • 100 kVA × 0.8 × 75% × 8 h = 480 kWh
  • 240 kWh ÷ (8 h × 0.8 × 75%) = 50 kVA

Convert kVA to kWh

Diesel generators are rated at 0.8 PF. Use 1.0 for purely resistive loads such as heaters.

Energy

480 kWh

Average output: 60 kW

100 kVA × 0.8 × 75% × 8 h = 480 kWh

Browse generators around 100 kVA: 100 kVA Generators

kVA to kWh table: generator energy output

kVA to kWh, PF 0.8, 75% average load
kVAkW at loadkWh per hourkWh per 8 hourskWh per 24 hours
10 kVA6648144
15 kVA9972216
20 kVA121296288
25 kVA1515120360
30 kVA1818144432
40 kVA2424192576
50 kVA3030240720
60 kVA3636288864
80 kVA48483841152
90 kVA54544321296
100 kVA60604801440
150 kVA90907202160
200 kVA1201209602880
250 kVA15015012003600
300 kVA18018014404320
400 kVA24024019205760
500 kVA30030024007200
600 kVA36036028808640
700 kVA420420336010080
800 kVA480480384011520
900 kVA540540432012960
1000 kVA600600480014400
1250 kVA750750600018000
1500 kVA900900720021600
2000 kVA12001200960028800
2500 kVA150015001200036000
3000 kVA180018001440043200

kWh to kVA table: generator size needed

kWh to kVA, 8 hours run time, PF 0.8, 75% target load
kWhkVA requiredNearest generator size
50 kWh10.4215 kVA generators →
100 kWh20.8325 kVA generators →
200 kWh41.6750 kVA generators →
250 kWh52.0860 kVA generators →
500 kWh104.17150 kVA generators →
750 kWh156.25200 kVA generators →
1000 kWh208.33250 kVA generators →
1500 kWh312.5400 kVA generators →
2000 kWh416.67500 kVA generators →
2500 kWh520.83600 kVA generators →
5000 kWh1041.671250 kVA generators →
7500 kWh1562.52000 kVA generators →
10000 kWh2083.332500 kVA generators →

kVA vs kWh: power vs energy

kVA is a rate: how much power a generator can deliver at any moment. kWh is a quantity: how much energy is delivered over time. Think of kVA as the size of the tap and kWh as the amount of water that has come out of it.

That's why you can't convert kVA straight to kWh. You also need to know:

  • Power factor: to turn kVA into kW (real power). Generators are rated at 0.8.
  • Load: generators rarely run flat out, so use the average percentage of the rating actually being drawn.
  • Time: how many hours the generator runs.

How to convert kVA to kWh

  1. Convert kVA to kW: multiply by the power factor (100 kVA × 0.8 = 80 kW).
  2. Apply the average load: 80 kW × 75% = 60 kW.
  3. Multiply by the hours: 60 kW × 8 hours = 480 kWh.

So a 100 kVA generator running at 75% load for an 8-hour working day produces about 480 kWh. At full load it produces 80 kWh every hour.

How to calculate kVA from kWh

Working backwards is how you size a generator from an energy figure:

  1. Divide the kWh by the hours to get the average kW (240 kWh ÷ 8 h = 30 kW).
  2. Divide by the power factor to get kVA (30 ÷ 0.8 = 37.5 kVA).
  3. Divide by your target load to build in headroom (37.5 ÷ 0.75 = 50 kVA).

Another example: a site using 1000 kWh over 24 hours needs about 69.4 kVA at 75% load and 0.8 PF, so an 80 kVA generator would suit.

One important caution: a kWh total only gives you the average demand. If your load has peaks, such as motors starting, kitchen equipment, or machinery running at the same time, size the generator for the peak, not the average. Our kW to kVA calculator is the better tool when you know your peak load in kW.

Why load % matters for diesel generators

Diesel generators are happiest working. Running a set at around 50-80% of its rating for most of its life is a good target. Running a diesel engine very lightly loaded for long periods can lead to "wet stacking": unburnt fuel and carbon building up in the exhaust. That's why it's worth not oversizing too far. The 75% default in this calculator builds sensible headroom into the result without leaving the generator underworked.

Estimating fuel from kWh

Once you know the kWh, you can estimate fuel use. As a rough guide, a diesel generator working at a reasonable load uses somewhere around 0.25-0.35 litres of fuel per kWh, so 480 kWh would need roughly 120-170 litres. Fuel efficiency varies by engine and load, so check the fuel consumption figures on each generator's product page for an accurate estimate. Browse our diesel generators to compare.

kVA to kWh FAQs

Can you convert kVA directly to kWh?

No. kVA is power and kWh is energy, so you need a time period. You also need a power factor to turn kVA into kW, and ideally the average load. The formula is kWh = kVA × PF × load % × hours.

How many kWh does a 100 kVA generator produce?

At full load and 0.8 PF, a 100 kVA generator produces 80 kWh per hour. At 75% load that's 60 kWh per hour, or 480 kWh over an 8-hour day.

How do I calculate the kVA I need from the kWh on my electricity bill?

Divide the kWh by the hours in the billing period to get your average kW, then divide by 0.8 to get kVA. Bear in mind this is an average: your peak demand will be higher. If your supplier provides half-hourly data or a maximum demand figure, size from that instead.

What load percentage should I enter?

Use 75% to size a new generator. That leaves headroom while keeping the engine well loaded. If you're calculating the output of an existing generator, enter its actual average load.

How do I convert kWh to kVA for a battery or solar system?

The same formula applies to any AC source: kVA = kWh ÷ (hours × PF × load %). For inverters, use the power factor from the inverter's specification.

Need help sizing a generator?

Tell us what you need to power and our team will recommend the right generator, with prices up front.