Find the current in amps for any load in kilowatts, on single phase or 3 phase supplies. Enter the kW, phase, voltage and power factor. The current updates instantly.
Single phase: I = (kW × 1000) ÷ (V × PF)
3 phase: I = (kW × 1000) ÷ (√3 × V × PF)
Where: I = current in amps (per phase for 3 phase) · kW = real power · V = voltage (line-to-line for 3 phase) · PF = power factor · √3 ≈ 1.732
Example: 100 kW, 3 phase 400V, PF 0.8: 100000 ÷ (1.732 × 400 × 0.8) = 180.4A per phase
UK mains: 230V single phase, 400V 3 phase (line-to-line). 110V is used for site tools.
Diesel generators are rated at 0.8 PF. Use 1.0 for purely resistive loads such as heaters.
Current
180.4A per phase
100000 ÷ (1.732 × 400V × 0.8) = 180.4A
Browse generators around 100 kW: 100 kW Generators
| kW | Amps per phase |
|---|---|
| 5 kW | 9.0 |
| 10 kW | 18.0 |
| 15 kW | 27.1 |
| 20 kW | 36.1 |
| 25 kW | 45.1 |
| 30 kW | 54.1 |
| 40 kW | 72.2 |
| 50 kW | 90.2 |
| 70 kW | 126.3 |
| 80 kW | 144.3 |
| 100 kW | 180.4 |
| 150 kW | 270.6 |
| 200 kW | 360.8 |
| 250 kW | 451.1 |
| 300 kW | 541.3 |
| 400 kW | 721.7 |
| 500 kW | 902.1 |
| 600 kW | 1082.5 |
| 700 kW | 1263.0 |
| 800 kW | 1443.4 |
| 900 kW | 1623.8 |
| 1000 kW | 1804.2 |
| 1500 kW | 2706.3 |
| 2000 kW | 3608.4 |
It depends on the voltage, the number of phases and the power factor. Here's how many amps 1 kW draws on common UK supplies:
| Supply | PF 1.0 (resistive) | PF 0.8 (typical generator load) |
|---|---|---|
| Single phase 230V | 4.35A | 5.43A |
| Single phase 110V (site tools) | 9.09A | 11.36A |
| 3 phase 400V (per phase) | 1.44A | 1.80A |
To find the amps for a bigger load, multiply these figures by the kW. Or use the calculator above, which does the conversion for any voltage and power factor.
Single phase: amps = kW × 1000 ÷ (volts × power factor)
3 phase: amps = kW × 1000 ÷ (1.732 × volts × power factor)
Multiplying by 1000 converts kilowatts to watts. Dividing by the voltage gives the current. The power factor is there because a load with a PF below 1 draws more current than its kW alone suggests. On 3 phase, the 1.732 (√3) accounts for the power being shared across three phases. The answer is the current in each phase.
| Load | Supply | Calculation | Amps |
|---|---|---|---|
| 3 kW heater | Single phase 230V, PF 1.0 | 3000 ÷ 230 | 13.0A |
| 10 kW | Single phase 230V, PF 0.8 | 10000 ÷ (230 × 0.8) | 54.3A |
| 100 kW | 3 phase 400V, PF 0.8 | 100000 ÷ (1.732 × 400 × 0.8) | 180.4A per phase |
| 400 kW | 3 phase 400V, PF 0.8 | 400000 ÷ (1.732 × 400 × 0.8) | 721.7A per phase |
The first row is why a standard 13A plug tops out at around 3 kW.
Most generators above small domestic sizes are 3 phase. When you convert kW to amps for 3 phase, the result is the current per phase, the figure you compare with breaker, cable and switchgear ratings. For example, a 100 kW generator at 400V and 0.8 PF delivers about 180A per phase, and a 400 kW generator about 722A per phase. Browse all 3 phase generators.
On a single phase 230V supply, 1 kW draws 4.35A at unity power factor, or 5.43A at 0.8 PF. On a 3 phase 400V supply it's 1.44A per phase at unity, or 1.80A per phase at 0.8 PF.
Divide the watts (kW × 1000) by the voltage and the power factor. For 3 phase, also divide by 1.732. The calculator above does it for you.
At 400V 3 phase and 0.8 PF, a 100 kW generator delivers about 180.4A per phase at full load.
A lower power factor means more current flows for the same useful power. At PF 0.8, a load draws 25% more current than the same kW at PF 1.0.
Yes. Current is measured in amps (amperes), so a kW to current conversion and a kW to amps conversion are the same calculation.
Use our Amps to kW calculator. For 3 phase, kW = 1.732 × amps × volts × PF ÷ 1000.