kVA to Amps Calculator

Work out the current in amps for any kVA rating, on a single phase or 3 phase supply. Enter the kVA, phase and voltage. The current per phase updates as you type.

Single phase: I = (kVA × 1000) ÷ V

3 phase: I = (kVA × 1000) ÷ (√3 × V)

Where: I = current in amps (per phase for 3 phase) · kVA = apparent power · V = voltage (line-to-line for 3 phase) · √3 ≈ 1.732

Example: 100 kVA, 3 phase 400V: 100000 ÷ (1.732 × 400) = 144.3A per phase

Convert kVA to Amps

⇄ Switch to Amps to kVA
Phase

UK mains: 230V single phase, 400V 3 phase (line-to-line). 110V is used for site tools.

No power factor needed: kVA already includes it.

Current

144.3A per phase

100000 ÷ (1.732 × 400) = 144.3A

Browse generators around 100 kVA: 100 kVA Generators

kVA to amps conversion table: single phase

kVA to amps, single phase 230V
kVAAmps
1 kVA4.3
2 kVA8.7
3 kVA13.0
5 kVA21.7
7.5 kVA32.6
10 kVA43.5
12 kVA52.2
15 kVA65.2
16 kVA69.6
20 kVA87.0
25 kVA108.7
30 kVA130.4
40 kVA173.9
50 kVA217.4

kVA to amps conversion table: 3 phase (per phase)

kVA to amps per phase, 3 phase 400V
kVAAmps per phase
10 kVA14.4
15 kVA21.7
20 kVA28.9
25 kVA36.1
30 kVA43.3
40 kVA57.7
50 kVA72.2
60 kVA86.6
80 kVA115.5
90 kVA129.9
100 kVA144.3
150 kVA216.5
200 kVA288.7
250 kVA360.8
300 kVA433.0
400 kVA577.4
500 kVA721.7
600 kVA866.0
700 kVA1010.4
800 kVA1154.7
900 kVA1299.0
1000 kVA1443.4
1250 kVA1804.2
1500 kVA2165.1
2000 kVA2886.8
2500 kVA3608.4
3000 kVA4330.1

How to convert kVA to amps

Because kVA already accounts for the power factor, you only need the voltage and the number of phases.

Single phase: multiply the kVA by 1000 to get VA, then divide by the voltage.
3 phase: multiply the kVA by 1000, then divide by √3 (1.732) × the line-to-line voltage.

kVASupplyCalculationAmps
10 kVASingle phase 230V10000 ÷ 23043.5A
20 kVA3 phase 400V20000 ÷ (1.732 × 400)28.9A per phase
100 kVA3 phase 400V100000 ÷ (1.732 × 400)144.3A per phase
500 kVA3 phase 400V500000 ÷ (1.732 × 400)721.7A per phase

Quick rules of thumb

  • 3 phase 400V: roughly 1.44A per kVA, per phase.
  • Single phase 230V: roughly 4.35A per kVA.

So a 20 kVA generator on a 3 phase 400V supply delivers about 29A per phase, and a 100 kVA generator about 144A per phase.

What does "amps per phase" mean?

On a 3 phase supply the load is shared across three live conductors. The figure from a kVA to amps per phase calculation is the current flowing in each of those conductors. It isn't a total to split three ways. Don't add the three phases together: a 100 kVA 3 phase generator is rated at about 144A per phase, not 433A.

Why the amps matter when choosing a generator

The kVA rating tells you how much power a generator can supply. The amps tell you what the rest of the installation has to be rated for:

  • Output breaker and protection: sized to the generator's full-load current.
  • Cables: the cable size from the generator to your distribution board depends on the current, cable length and installation method.
  • ATS panels and changeover switches: rated in amps. A standby generator's automatic transfer switch must be rated at or above the generator's full-load current, so for a 100 kVA, 400V set (144A per phase) you'd choose the next standard rating up, typically 160A.
  • Site distribution: temporary site distribution boards and sockets are rated in amps too, including 110V tool circuits.

Your electrician or electrical designer will confirm cable and protection sizes. Converting kVA to amps first gives you the numbers to start that conversation.

Single phase or 3 phase?

UK homes and small businesses usually have a single phase 230V supply. Larger commercial, agricultural and industrial sites usually have 3 phase 400V. Choose the phase that matches the supply you're backing up or the equipment you're powering. Browse 3 phase generators or single phase generators.

kVA to Amps FAQs

How many amps is 100 kVA?

On a 3 phase 400V supply, 100 kVA is 144.3A per phase. On a single phase 230V supply it would be 434.8A, which is why sets this size are almost always 3 phase.

Do I need the power factor to convert kVA to amps?

No. kVA is apparent power, so it already includes the effect of the power factor. You only need the voltage and whether the supply is single phase or 3 phase. Converting from kW to amps does need a power factor: use our kW to Amps calculator.

How many amps per phase is a 20 kVA generator?

About 28.9A per phase at 400V 3 phase, or 87A on a single phase 230V supply.

What voltage should I use?

In the UK, use 230V for single phase and 400V for 3 phase (line-to-line). Some older equipment is labelled 240V or 415V. 110V is used for site power tools.

How do I convert amps back to kVA?

Use our Amps to kVA calculator. For 3 phase, kVA = √3 × amps × volts ÷ 1000.