Generator for a Heat Pump and EV Charger: What Size You Need

Generator for a Heat Pump and EV Charger: What Size You Need

24th Nov 2026

Quick answer

Yes, with the right generator. A UK air source heat pump typically draws a few kilowatts when running, for example about 15 A (roughly 3.5 kW) for a 7 kW Vaillant model, and a home EV charger takes up to 7.4 kW at 32 A. With normal house loads, running everything at once can reach 15 to 18 kW, so you need a single-phase set rated well above that, such as a 20 kW or 27 kW prime generator. You can lower the load by limiting the charger's current, which some chargers allow down to 6 A. Check your heat pump's data plate for its running and starting current before choosing, and have a qualified electrician fit the transfer switch.

Heat pumps and EV chargers are now two of the biggest loads in many UK homes, and both stop in a power cut. People who add either one often ask the same question: what generator would keep them running?

The answer depends on three things: how much your heat pump actually draws, how you set up the charger, and whether your home is single or three phase. This guide explains how to find the real numbers, shows worked examples against single-phase sets from our range, and covers the starting current question that causes the most worry. It is general guidance. Your heat pump's own manual and your installer should confirm the figures for your home.

What does a heat pump draw?

A heat pump's electrical input is much lower than its heat output, because it moves heat rather than making it. The figures to look for are on the data plate and in the installation manual: rated current, in-rush or starting current, and the recommended fuse size.

Vaillant's aroTHERM plus range is a typical UK example. Its published data for 230 V single-phase models shows:

Model size Maximum rated current Approx. power at 230 V In-rush current
5 kW 14.3 A About 3.3 kW 14.3 A
7 kW 15.0 A About 3.45 kW 15.0 A
12 kW (230 V) 23.3 A About 5.4 kW 23.3 A

The 7 kW model specification lists a 16 A fuse. These figures are from one manufacturer, so treat them as an example, not a rule.

Backup heaters and immersion elements

Many heat pump systems also have an electric backup heater or an immersion element for hot water. Vaillant's hydraulic module instructions list internal backup heater stages up to 5.4 kW, and up to 8.54 kW on its 12 kW model at 230 V. A typical immersion heater adds about 3 kW. These are easy to forget, and they can double the load, so decide whether to run them from a generator.

What about starting current?

Starting current is the heart of the question. A large compressor motor started across the line can draw several times its running current. That is why generator advice often warns heat pumps are hard to start.

Modern heat pumps usually avoid this. Kensa, a UK heat pump maker, describes two approaches for single-phase units:

  • A three-phase compressor driven by an inverter, which solves the starting current problem.
  • A single-phase compressor with an electronic limiter, which typically reduces the inrush to about a quarter of the direct-on-line current.

Manufacturer data confirms the effect. The Vaillant 7 kW specification lists an in-rush current of 15.0 A, the same as its maximum rated current, and its data sheet notes the figure is with an inrush current limiter. One older Daikin heat pump data sheet lists soft start for both its compressors and fans.

Not every heat pump is the same, though. Some older or simpler models start across the line. Check your own data plate and installation manual for the starting method and the in-rush figure, and if it is not clear, ask the installer or the manufacturer.

What does an EV charger draw?

A typical UK home EV charger is rated at up to 7 kW or 7.4 kW from a 32 A single-phase 230 V supply. Manufacturers' data sheets for common chargers list rated current of 32 A. A three-phase charger can go up to 22 kW.

Many chargers let you lower the maximum charging current, which is the simplest way to fit a charger to a generator, though the range varies by model. One manufacturer's data sheet lists an adjustable current of 6 A to 32 A, and another charger allows the maximum current to be set in its app.

Charger setting Approx. load at 230 V
32 A (full rate) About 7.4 kW
16 A About 3.7 kW
6 A (minimum on some chargers) About 1.4 kW

Check the charger works on generator power

EV chargers have protections that can trip when the supply behaves differently from the mains. Data sheets give a supply voltage tolerance, for example 230 V plus or minus 10% on one charger and wider on others. Many UK chargers also have built-in PEN fault detection, which UK wiring rules require for outdoor chargers on PME supplies, and which disconnects the charger if it detects a problem with the neutral and earth. Ask the charger manufacturer and your installer whether the charger is compatible with generator supply and how the earthing arrangement affects it. Our generator earthing requirements guide explains the basics.

Putting it together: three worked examples

These examples use the Vaillant 7 kW figures, a 7.4 kW charger and a typical set of house essentials (fridge-freezer, lighting, boiler controls, TV and router, kettle) of about 4.3 kW. The loads are illustrative. Your own figures will differ.

Scenario Total load
A. Essentials, heat pump and charger limited to 16 A 4.3 + 3.5 + 3.7 = about 11.5 kW
B. Essentials, heat pump, a 3 kW backup or immersion heater and a full 7.4 kW charger 4.3 + 3.5 + 3 + 7.4 = about 18.2 kW
C. Essentials and heat pump only 4.3 + 3.5 = about 7.8 kW

Which single-phase generators fit?

Most UK homes have a single-phase supply, so a single-phase set suits. These models from our range show how the scenarios fit. The percentages are of the rating shown:

Generator Rating Scenario A (11.5 kW) Scenario B (18.2 kW) Scenario C (7.8 kW)
Pramac GA10000 (gas, standby only) 10 kW Too high Too high 78%
Pramac GA13000 (gas, standby only) 13 kW 88% Too high 60%
Pramac P11000-1P (diesel) 9 kW prime Too high Too high 87%
Cummins C28D5-1P (diesel) 20 kW prime 58% 91% 39%
Cummins C38D5-1P (diesel) 27 kW prime 43% 67% 29%

Four points follow from the table:

  • For a heat pump alone (scenario C), a 10 kW or 13 kW set is enough.
  • For a heat pump and a charger, limit the charger to about 16 A on the smaller sets, or choose 20 kW or more.
  • For everything at once, including backup heating and a full-rate charger, the C28D5-1P is near its limit and the C38D5-1P has room.
  • The gas sets are standby-only, with no prime rating, so they are meant for outages, not daily use. Browse our gas generators for the range.

For regular running, keep the typical load under about 80% of the prime rating. Our guide to what a 20 kVA generator can run and our 30 kVA generators give more detail on the sizes either side, and our generators for homes page covers home backup in general.

What if you have three-phase power?

Three-phase heat pumps, usually larger units, need a three-phase generator. But a three-phase generator only gives each phase about a third of its total for single-phase loads. A 20 kVA set, for example, carries about 6.7 kVA per phase on its prime rating, so a 7.4 kW single-phase charger would exceed one phase. Limiting it to 16 A (about 3.7 kW) would fit. Our guide to single phase vs three phase explains the issue, and you can browse our single phase generators and 3 phase generators.

A practical plan

  1. Find the data. Note your heat pump's running current, starting current and fuse size, plus any backup heater and immersion ratings.
  2. Decide what must run in an outage. In a power cut, heating and hot water usually matter more than charging a car.
  3. Set the charger. Limit its current so it fits the generator, or schedule charging when the heat pump is idle.
  4. Add the house essentials and total the loads you will run together.
  5. Choose a generator so the typical load stays under about 80% of the prime rating, or within the standby rating for outage-only use.
  6. Have it installed properly, with a transfer switch fitted by a qualified electrician. Our guide to automatic versus manual transfer switches explains the options.

> Not sure what your home needs? Send us your heat pump model, charger rating and supply type, and we will help you choose a set. Use the contact page or call +44 1302 700200.

Run time, noise and safety

A home generator may run for hours, so check the fuel. Our guide to how to calculate generator runtime shows how to estimate it. Silent canopied sets reduce noise, and our guide to how quiet a silent generator really is explains how to read the figures.

Never run a generator indoors, because the exhaust contains carbon monoxide. Connection must go through a changeover arrangement fitted by a qualified electrician, never a plug, and the HSE's electrical safety guidance covers the general principles. For heat pump specifications, see the manufacturer's own documents, for example the Vaillant aroTHERM plus 7 kW specification, and Kensa's explanation of heat pumps and single-phase power.

Frequently asked questions

Can a generator run a heat pump?

Yes, in most cases. Check the heat pump's running current, starting current and fuse size, and choose a generator rated comfortably above them. Many modern heat pumps use inverter drives or inrush limiters that keep the starting current low, but some start across the line.

What size generator do I need for a heat pump?

For a 5 to 7 kW heat pump drawing about 3.3 to 3.5 kW, a 10 kW or 13 kW single-phase set can cover it with the house essentials. Add any backup or immersion heater and size from the total. Larger units, such as a 12 kW model at about 5.4 kW, need a bigger set.

Can a generator charge an electric car?

Yes, but a full-rate home charger takes up to 7.4 kW. Limit the charger's current, for example to 16 A (about 3.7 kW), if the generator is small. Check that the charger is compatible with generator supply.

Will a heat pump's starting current overload a generator?

Usually not with a modern inverter-driven or soft-start unit, but check. The Vaillant 7 kW heat pump's in-rush current equals its 15 A maximum running current. A heat pump that starts across the line can draw several times its running current.

Can I run a heat pump and EV charger together?

Yes, with a generator large enough for both plus the house loads. On a 20 kW prime set, scenario A (about 11.5 kW) is about 58% load, but a full-rate charger with a backup heater (about 18.2 kW) takes it to about 91%.

Do I need a transfer switch?

Yes. A qualified electrician should fit a changeover or automatic transfer switch, so the generator never feeds back into the network and your home switches over safely.

Conclusion

A generator can run a heat pump and an EV charger, but only if you size it from real numbers. Find your heat pump's running and starting current, include any backup heating, set the charger to suit and choose a single-phase set that keeps your typical load under about 80% of its prime rating. Then have a qualified electrician fit the transfer switch.

> Talk to a real person: Global Generators is an authorised Cummins reseller and an authorised Grupel and Pramac dealer, with new diesel generators in stock for UK delivery and export. Browse the stock list, then contact our team on +44 1302 700200 or at enquiries@global-generators.com and we will help you match a set to your home.