Quick answer
A diesel generator's warranty depends on the rating it is used under. Standby cover is usually longer in years but capped at a low number of running hours, while prime cover is shorter in years but allows far more hours. On the sets we list, Cummins standby cover is two years or 500 hours and prime is one year with unlimited hours, and Pramac standby cover is two years or 1,000 hours and prime is one year or 3,000 hours. A generator that runs most days can use up a standby hour limit in a few months, so match the rating to how you will really use the set, and read the written warranty statement for your exact model.
This guide explains how those limits work, shows real terms from manufacturers' published statements and from the sets in our range, and gives a checklist to use before you buy. It is general guidance. The written warranty statement for your model is the authority, and manufacturers publish different versions for different ranges and regions.
Why the rating sets the cover
Generators are rated by how they will be used, under the standard ISO 8528-1. A warranty then ties its cover to that rating.
- Emergency standby power (ESP) is for supplying a site during a mains failure, or under test conditions. A Cummins Power Generation warranty statement defines it as up to 500 hours of operation per year, with the average output over 24 hours not exceeding 70% of the rating.
- Prime power (PRP) is for supplying a variable load for an unlimited number of hours per year. The same statement says the average output over 24 hours should not exceed 70% of the prime rating, and that applications needing a higher average should use a continuous rating.
Two things follow. First, test runs count towards the hours. Second, using a generator outside its designated rating is a listed reason a claim can be refused. Our guides to prime versus standby power and standby versus prime rating on a 500 kVA generator explain the ratings in detail.
What the hour limit means in practice
The limit is a number of hours, not a number of years, and cover ends when either runs out. This table shows how quickly the hours go at different running patterns:
| How the generator runs | Hours per year | Time to reach 500 hours | Time to reach 1,000 hours | Time to reach 3,000 hours |
|---|---|---|---|---|
| Weekly 1-hour test only | About 52 | Over 9 years | Over 19 years | Over 57 years |
| Two outages of 12 hours plus testing | About 80 | About 6 years | About 12 years | About 37 years |
| 10 hours every day | About 3,650 | About 50 days | About 100 days | About 300 days |
For a generator used only as emergency backup, a standby limit lasts the whole warranty period. For a generator that runs for 10 hours a day, as in an off-grid charging site, a standby hour limit is gone in two or three months, even though the years have barely started. In that case the set should be bought, rated and warranted for prime duty.
Real terms from our range and from manufacturers
The terms below are from our product pages and from the manufacturers' own published statements. They are examples. Check the statement for your own model.
| Source | Standby cover | Prime cover |
|---|---|---|
| Cummins sets listed on our product pages | 2 years or 500 hours | 1 year, unlimited hours |
| Pramac GBW22P and P11000 on our product pages | 2 years or 1,000 hours | 1 year or 3,000 hours |
| Pramac statement, stationary diesel generators | 2 years or 1,000 hours | 1 year or 3,000 hours (6,000 hours for high power diesel) |
| Pramac statement, rental and mobile diesel generators | Not applicable | 1 year, unlimited hours |
| Cummins Power Generation commercial statement (Issue 5, 2017) | 24 months or 1,000 hours | 12 months, unlimited hours |
| Pramac GA gas generators on our product pages | 5-year limited warranty, with a 10-year extended warranty available | Standby only |
The Cummins rows show why you must read the right document. Cummins publishes several warranty statements, and their standby terms differ. The Cummins Power Generation commercial statement above gives 24 months or 1,000 hours, and a Cummins Sales and Service generator set statement shows different standby hour limits again, with a prime limit that total operating time at 100% of the prime rating must not exceed 500 hours per year. Alternators are covered separately. Cummins Generator Technologies' Stamford alternator statement gives standby cover of 24 months from start-up or 1,000 hours, limited to 500 hours per year, and 12 months with unlimited hours for continuous and prime.
You can read the Pramac terms in the Pramac warranty statement for power generators, and one of the Cummins terms in a Cummins generator set warranty statement.
> Expert tip: Ask for the warranty statement that applies to the exact model and serial number, and check the hour limit wording: total hours, or hours per year. Some statements cap standby at a number of hours per year, and others at a total.
When does the warranty start?
The start date matters, because the clock can start before you switch the set on.
- Pramac: coverage starts from the date of shipment from the factory. Registering the unit restarts the warranty period, up to six months after the shipment date, and start-up inspection must be carried out by an authorised service dealer.
- Cummins Power Generation (Issue 5, 2017): the start date is the date of initial start-up, first rental, demonstration or 18 months after the factory ship date, whichever is sooner.
If a generator sits in storage, or waits months for installation, find out when cover began and what evidence of commissioning is needed.
What a warranty usually covers
The statements we reviewed cover defects in material or workmanship under normal use. The Cummins statement says it covers parts and labour to repair the product, reasonable travel expenses to the site, and maintenance items damaged by a warrantable failure. The Pramac statement says the manufacturer will repair or replace parts found defective under normal use, through an authorised service dealer, and notes that engines and alternators carry their own manufacturers' warranties, handled through those dealer networks.
What it usually excludes
Both documents list conditions that can end or limit cover. Common ones include:
- Use outside the designated rating or application guidelines, such as running a standby set as a prime source.
- Improper installation or sizing. Pramac lists this directly.
- Lack of maintenance or unauthorised repair, and failure to follow the manufacturer's published guidelines.
- Contaminated or improper fuel, coolant or lubricant.
- Normal wear and tear, routine maintenance costs and, in the Pramac statement, batteries as wear components.
- Misuse, accident, negligence or modification.
- Improper storage before or after commissioning, in the Cummins statement.
- Consequential losses. Both documents exclude downtime, lost revenue and similar knock-on costs, and the Cummins statement makes the owner responsible for rental of replacement sets and for downtime expenses.
Costs outside normal working hours are also limited. The Pramac statement says overtime, holiday or emergency labour is the customer's responsibility, and the Cummins statement makes labour overtime and premium shipping requested by the owner the owner's cost.
Maintenance records and who does the work
Both manufacturers expect you to maintain the set and to be able to prove it.
- Pramac recommends that scheduled maintenance be carried out by an authorised service dealer, says verification of required maintenance may be required for coverage, and its claim form asks for the current running hours, the application and the maintenance history.
- The Cummins statement requires the owner to notify the distributor or dealer within 30 days of discovering a failure, to provide evidence of the commissioning date, and to install, operate and maintain the product in line with its published guidelines.
Keep service records, running hours, fuel records and commissioning paperwork together. Our backup generator maintenance guide, our guide to when generators need servicing and our guide to how often generators should be tested set out a sensible routine. Because contaminated fuel is excluded, read our guide to generator fuel contamination and site uptime too.
Sizing, installation and transfer switches
Because "improper installation or sizing" and "inappropriate use relative to designated power rating" appear in the exclusions, getting the specification right protects your cover. Our guide to sizing a generator around critical loads explains how to do it.
The Pramac statement also recommends an original load transfer switch, and says that if a non-original switch is used and directly causes damage to the generator, no warranty coverage applies. Our guides to automatic versus manual transfer switches and generator ATS installation cover the switching side. The Pramac statement also says the warranty is not transferable, so a claim must be made by the original owner.
Which rating suits which use?
| Your use | Usual rating | Why |
|---|---|---|
| Emergency backup for a reliable mains supply, with regular testing | Standby | Long cover in years, with hours well within the cap |
| Regular daily or weekly running | Prime | Hour limits are far higher or unlimited |
| Hybrid or off-grid charging, run most days | Prime | A standby hour limit would be used up quickly |
| Rental or mobile use | Check the product group's terms | Some statements give rental and mobile sets unlimited hours for one year |
For the main duty-related questions, see our standby generators range, and browse the Cummins and Pramac ranges.
A checklist before you buy
- Which rating is the generator warranted for? Standby, prime or both?
- What is the hour limit, and is it total hours or hours per year?
- When does cover start, at shipment or at commissioning, and what proves it?
- Who carries out the work, and does it have to be an authorised dealer?
- What maintenance evidence is needed, and how often?
- Are the engine and alternator covered by separate warranties?
- What is excluded, including fuel, installation, sizing and transfer switch requirements?
- What costs fall on you, such as travel, overtime, rental and downtime?
> Want the warranty terms for a specific model? Tell us the generator you are considering and how you will use it, and we will point you to the warranty statement that applies. Use the contact page or call +44 1302 700200.
Frequently asked questions
Does using a standby generator every day void the warranty?
It can take the generator outside its cover. Warranty statements tie cover to the designated rating and list use outside it as a reason a claim may be refused, and standby cover has a low hour limit. If the set will run regularly, buy it rated and warranted for prime use.
What does 500 hours on a standby warranty mean?
It is the running-hour limit for the cover, and the warranty ends when the hours or the years run out, whichever comes first. Some statements apply the cap per year and some as a total, so read the wording. Test runs count towards the hours.
When does a generator warranty start?
It depends on the manufacturer. Pramac cover starts at shipment, restarted by registration up to six months later. A Cummins Power Generation statement starts it at initial start-up, first rental or demonstration, or 18 months after ship date, whichever is sooner.
Do I need service records to keep the warranty?
Yes, you should. The manufacturers' statements list lack of maintenance as an exclusion, and Pramac says verification of maintenance may be required. Keep dated service records, hours and fuel records.
Is a generator warranty transferable?
The Pramac statement says its warranty is not transferable, so claims must come from the original owner. Check the statement for your model, because terms differ.
Who handles a warranty claim?
Usually an authorised dealer or distributor for the manufacturer. Pramac says warranty repairs must be performed or addressed by its authorised service dealers, and the Cummins statement requires you to notify the distributor or dealer within 30 days of discovering a failure.
Conclusion
A generator warranty is a set of conditions tied to a rating, not just a number of years. Choose standby or prime to match how the set will actually run, check the hour limit and when cover starts, keep records, use the right installation and transfer equipment, and read the written statement for your model before you buy.
> Talk to a real person: Global Generators is an authorised Cummins reseller and an authorised Grupel and Pramac dealer, with new diesel generators in stock for UK delivery and export. Browse the stock list, then contact our team on +44 1302 700200 or at enquiries@global-generators.com and we will help you choose the right set and rating.